CVE-2026-3611
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Threat Intelligence Signals
Identity & Timeline
| Status | - |
| Assigning Authority | - |
| CVSS Version / Source | - |
| Reserved | - |
| Published | - |
| Patch Date (date_public) | - |
| Exploit DB Date | - |
| First GitHub PoC Date | - |
| Last Updated | - |
| Time to Patch (Days to fix) | - |
| Exploit Release Gap | - |
| PoC Release Gap | - |
| Exploit DB References | None identified |
Affected Products & Versions
| Vendor | Product | Affected Versions |
|---|---|---|
| No affected products specified. | ||